This standard regulates the installation and maintenance of assemblies and devices used to protect openings in walls floors and ceilings against the spread of fire and smoke within into or out of buildings.
Electrical room door fire rating requirements.
Vaults are definitely different from electrical rooms.
Where equipment rated 1200 a or more that contains overcurrent devices switching devices or control devices is installed and there is a personnel door s intended for entrance to and egress from the working space less than 7 6 m 25 ft from the nearest edge of the working space the door s shall open in the direction of egress and be.
1 1 1 with the exception of fabric fire safety curtain assemblies this standard addresses assemblies that have.
A 1 1 see annex k for general information about fire doors.
Nfpa 75 appendix c fig b 1.
Electrical room exit requirement jbartos electrical 22 apr 04 22 14.
Please note that electrical room may require fire rated walls see nfpa 110 5 2 1 5 2 2.
You are correct that electrical vaults containing equipment with 600 amps or greaters must have at least 3 hour rated walls and 3 hour rated floors if there are any floors underneath the vault.
Locating electrical rooms next to these especially if placed between should be carefully evaluated to ensure there is enough space and flexibility for conduits.